General Information
D-011-0152 13
Access Control and Passwords
The EA800 console is normally locked to prevent unauthorized use. The currently active function of the F1 soft key
(UNLOCK or LOCK) is displayed above the key. The locked and unlocked states are described below.
Note: The console locks automatically after 30 minutes of inactivity if the user does not press the LOCK soft key
(F1).
Locked: This is the default state and limits access to the EA800 to viewing only.
UNLOCK is displayed above the F1 soft key indicates that the console is currently
locked. Pressing the F1 soft key prompts the user to enter a password to unlock
the console, permitting full access to all screens and functions. The HOME key,
MENU key, and the MAIN MENU options shown on the screen at right are
available to the user when the console is locked.
Unlocked: When the console is unlocked, LOCK displayed above the F1 soft key, and all information,
programming, and maintenance screens may be viewed and programming changes may be made. Pressing
the F1 soft key locks the EA800 console and protects it from unauthorized or unintended programming
changes, log downloads, and firmware uploads.
The console allows the use of two passwords for unlocking:
The factory default password is 0800. This password cannot be changed or deleted.
A second, optional password may be set by the user. To create a second user password, see “Changing the
Password” on page 48.
System Configuration Parameters
The EA800 console requires certain system level information as outlined in Table 4.
Table 4 System Configuration Parameters
Parameter Selections Factory Default Description
Date Format MM/DD/YYYY
DD/MM/YYYY
MM/DD/YYYY Sets the desired date format for all event time stamps.
Time Format 12-hour
24-hour
24-hour Sets the desired time format for all event time stamps.
Data
Collection
Frequency
30 seconds*
1 minute*
5 minutes
15 minutes
30 minutes
60 minutes
•120 minutes
* Settings not
available on
EA800-ip while
connected to
network
5 minutes Sets the interval for collecting and recording data from the
sensors. The data collection frequency applies to all sen-
sors.The EA800 provides approximately 10,000 data
points to be collected regardless of the frequency
selected. The estimated time duration covered for each
data collection frequency is listed below.
30 seconds = 3.5 days
1 minute = 1 week
5 minutes = 1 month
15 minutes = 3 months
30 minutes = 6 months
60 minutes = 1 year
120 minutes = 2 years